Read Holding Registers (Function Code=03)
Request
This command is requesting the content of analog output holding registers
# 40108 to 40110 from the slave device with address 17.
11 03 006B 0003 7687
11: The Slave Address
(11 hex = address17 )
03: The Function Code 3 (read Analog Output Holding Registers)
006B: The Data Address
of the first register requested.
(
006B hex = 107 , + 40001
offset = input #40108 )
0003: The total number of registers requested. (read 3 registers 40108 to 40110)
7687: The CRC (cyclic redundancy check) for error checking.
Response
11 03 06 AE41 5652 4340 49AD
11: The Slave Address
(11 hex = address17 )
03: The Function Code 3 (read Analog Output Holding Registers)
06: The number of data bytes to follow (3 registers x 2 bytes each = 6 bytes)
AE41: The contents of register 40108
5652: The contents of register 40109
4340: The contents of register 40110
49AD: The CRC (cyclic redundancy check).