Simply Modbus logo

 


Home

About
MODBUS
fc01
fc02
fc03
fc04
fc05
fc06
fc15
fc16
ASCII
TCP
exceptions

About
Enron
MODBUS


RTU Master

RTU Slave

TCP Client

Download

Purchase

Contact

 

Frequently Asked Questions

What is Modbus?

What is it used for?

How does it work?

What is hexadecimal?

How is data stored in Standard Modbus?

What is a function code?

What is a CRC?

What are the formats of Modbus commands and responses?

What are data types?

What is byte and word ordering?

What is a Modbus Map?

What is the difference between Modbus ASCII and Modbus RTU?

What are extended register addresses?

How does 2-byte addressing work?

How can you send events and historical data?

What is Enron Modbus?

What else?

 

What is Modbus?

Modbus is a serial communication protocol developed by Modicon published by Modicon® in 1979 for use with its programmable logic controllers (PLCs). In simple terms, it is a method used for transmitting information over serial lines between electronic devices. The device requesting the information is called the Modbus Master and the devices supplying information are Modbus Slaves. In a standard Modbus network, there is one Master and up to 247 Slaves, each with a unique Slave Address from 1 to 247. The Master can also write information to the Slaves.

The official Modbus specification can be found at modbus.org/specs.php .

What is it used for?

Modbus is an open protocol, meaning that it's free for manufacturers to build into their equipment without having to pay royalties. It has become a standard communications protocol in industry, and is now the most commonly available means of connecting industrial electronic devices. It is used widely by many manufacturers throughout many industries. Modbus is typically used to transmit signals from instrumentation and control devices back to a main controller or data gathering system, for example a system that measures temperature and humidity and communicates the results to a computer. Modbus is often used to connect a supervisory computer with a remote terminal unit (RTU) in supervisory control and data acquisition (SCADA) systems. Versions of the Modbus protocol exist for serial lines (Modbus RTU and Modbus ASCII) and for Ethernet (Modbus TCP).

How does it work?

Modbus is transmitted over serial lines between devices. The simplest setup would be a single serial cable connecting the serial ports on two devices, a Master and a Slave.

         DB9 connector         voltage stripchart>

The data is sent as series of ones and zeroes called bits. Each bit is sent as a voltage. Zeroes are sent as positive voltages and a ones as negative. The bits are sent very quickly. A typical transmission speed is 9600 baud (bits per second).

What is hexadecimal?

When troubleshooting problems, it can be helpful to see the actual raw data being transmitted. Long strings of ones and zeroes are difficult to read, so the bits are combined and shown in hexadecimal. Each block of 4 bits is represented by one of the sixteen characters from 0 to F.

0000 = 0 0100 = 4 1000 = 8 1100 = C
0001 = 1 0101 = 5 1001 = 9 1101 = D
0010 = 2 0110 = 6 1010 = A 1110 = E
0011 = 3 0111 = 7 1011 = B 1111 = F

Each block of 8 bits (called a byte) is represented by one of the 256 character pairs from 00 to FF.

What is ASCII?

ASCII stand for American Standard Code for Information Interchange.  In the same way that every 4 bits can be combined and represented by one of sixteen hexadecimal characters from 0 to F, every 8 bits (every byte) can be combined and represented by one of 256 ASCII characters, including the common keyboard characters.   For example, some of the values for ASCII characters are...

decimal
(base10)
binary
(base2)
Hex
(base16)
ASCII
(base256)
0 0000 0000 00 null
1 0000 0001 01 "
34 0010 0010 22 #
35 0010 0011 23 $
36 0010 0100 24 %
47 0010 1111 2F /
48 0011 0000 30 0
49 0011 0001 31 1
56 0011 1000 38 8
57 0011 1001 39 9
58 0011 1010 3A :
64 0100 0000 40 @
65 0100 0001 41 A
66 0100 0010 42 B
89 0101 1001 59 Y
90 0101 1010 5A Z
91 0101 1011 5B [
95 0101 1111 5F _
96 0110 0000 60 `
97 0110 0001 61 a
122 0111 1010 7A z
123 0111 1011 7B {
174 1010 1110 AE ®
255 1111 1111 FF  

 

How is data stored in Standard Modbus?

Information is stored in the Slave device in four different tables.
Two tables store on/off discrete values (coils) and two store numerical values (registers). The coils and registers each have a read-only table and read-write table.

Each table has 9999 values.
Each coil or contact is 1 bit and assigned a data address between 0000 and 270E.
Each register is 1 word = 16 bits = 2 bytes and also has data address between 0000 and 270E.

Coil/Register Numbers

Data Addresses

Type Table Name

1-9999

0000 to 270E

Read-Write Discrete Output Coils

10001-19999

0000 to 270E

Read-Only Discrete Input Contacts

30001-39999

0000 to 270E Read-Only Analog Input Registers

40001-49999

0000 to 270E Read-Write Analog Output Holding Registers

Coil/Register Numbers can be thought of as location names since they do not appear in the actual messages. The Data Addresses are used in the messages.

For example, the first Holding Register, number 40001, has the Data Address 0000.
The difference between these two values is the offset.
Each table has a different offset. 1, 10001, 30001 and 40001.

What is the Slave ID?

Each slave in a network is assigned a unique unit address from 1 to 247. When the master requests data, the first byte it sends is the Slave address. This way each slave knows after the first byte whether or not to ignore the message.

What is a function code?

The second byte sent by the Master is the Function code. This number tells the slave which table to access and whether to read from or write to the table.

Function Code Action Table Name
01 (01 hex) Read Discrete Output Coils
05 (05 hex) Write single Discrete Output Coil
15 (0F hex) Write multiple Discrete Output Coils
02 (02 hex) Read Discrete Input Contacts
04 (04 hex) Read Analog Input Registers
03 (03 hex) Read Analog Output Holding Registers
06 (06 hex) Write single Analog Output Holding Register
16 (10 hex) Write multiple Analog Output Holding Registers

What is a CRC?

CRC stands for Cyclic Redundancy check.  It is two bytes added to the end of every modbus message for error detection.  Every byte in the message is used to calculate the CRC. The receiving device also calculates the CRC and compares it to the CRC from the sending device. If even one bit in the message is received incorrectly, the CRCs will be different and an error will result.

Here is a spreadsheet CRC calculator for messages up to 16 bytes.
To download a copy, right click and select Save Target As...

What are the formats of Modbus commands and responses?

Follow the links in this table to see examples of the requests and responses.

Data Addresses Read Write Single Write Multiple
Discrete Output Coils 0xxxx FC01 FC05 FC15
Discrete Input Contacts 1xxxx FC02 NA NA
Analog Input Registers 3xxxx FC04 NA NA
Analog Output Holding Registers 4xxxx FC03 FC06 FC16

                                                                           FC = Function Code

What are data types?

The example for FC03 shows that register 40108 contains AE41
which converts to the 16 bits 1010 1110 0100 0001
Great! But what does it mean? Well, it could mean a few things.

Register 40108 could be defined as any of these 16-bit data types:
     A 16-bit unsigned integer (a whole number between 0 and 65535)
                    register 40108 contains AE41 = 44,609 (hex to decimal conversion)

     A 16-bit signed integer (a whole number between -32768 and 32767)
                                                        AE41 = -20,927
              (hex to decimal conversion that wraps, if its over 32767 then subtract 65536)

     A two character ASCII string (2 typed letters)
                                                        AE41 = ® A

     A discrete on/off value (this works the same as 16-bit integers with a value of 0 or 1.
                                              The hex data would be 0000 or 0001)

Register 40108 could also be combined with 40109 to form any of these 32-bit data types:
     A 32-bit unsigned integer (a number between 0 and 4,294,967,295)
                             40108,40109 = AE41 5652 =  2,923,517,522

     A 32-bit signed integer (a number between -2,147,483,648 and 2,147,483,647)
                                                       AE41 5652 = -1,371,449,774

      A 32-bit single precision IEEE floating point number.
      This is a mathematical formula that allows any real number (a number with decimal
       points) to represented by 32 bits with an accuracy of about seven digits.
                                                       AE41 5652 = -4.395978 E-11

      Here is a spreadsheet IEEE float calculator for inputs of 4 bytes or 2 words.
      To download a copy, right click and select Save Target As...

     A four character ASCII string (4 typed letters)
                                                         AE41 5652 = ® A V R

More registers can be combined to form longer ASCII strings.  Each register being used to store two ASCII characters (two bytes).

What is byte and word ordering?

The Modbus specification doesn't define exactly how the data is stored in the registers. Therefore, some manufacturers implemented modbus in their equipment to store and transmit the higher byte first followed by the lower byte. (AE before 41).
Alternatively, others store and transmit the lower byte first (41 before AE).

Similarly, when registers are combined to represent 32-bit data types, Some devices store the higher 16 bits (high word) in the first register and the remaining low word in the second (AE41 before 5652) while others do the opposite (5652 before AE41)

It doesn't matter which order the bytes or words are sent in, as long as the receiving device knows which way to expect it.

For example, if the number 2,923,517,522 was to be sent as a 32 bit unsigned integer, it could be arranged any of these four ways.

                                                                                             also know as
     AE41 5652       high byte first      high word first    "big endian"
     5652 AE41       high byte first      low word first
     41AE 5256       low byte first      high word first
     5256 41AE       low byte first      low word first     "little endian"

What is a Modbus Map?

A modbus map is simply a list for a slave device that defines
            - what the data is (eg. pressure or temperature readings)
            - where the data is stored (which tables and data addresses)
            - how the data is stored (data types, byte and word ordering)

Some devices are built with a fixed map that is defined by the manufacturer. While other devices allow the operator to configure or program a custom map to fit their needs.

What is the difference between Modbus ASCII and Modbus RTU?

The difference between these two modes is explained here.

What are extended register addresses?

Since the range of the analog output holding registers is 40001 to 49999, it implies that there cannot be more than 9999 registers. Although this is usually enough for most applications, there are cases where more registers would be beneficial.

Registers 40001 to 49999 correspond to data addresses 0000 to 270E.   If we utilize the remaining data addresses 270F to FFFF, over six times as many registers can be available, 65536 in total.  This would correspond to register numbers from 40001 to 105536.

Many modbus software drivers (for Master PCs) were written with the 40001 to 49999 limits and cannot access extended registers in slave devices. And many slave devices do not support maps using the extended registers. But on the other hand, some slave devices do support these registers and some Master software can access it, especially if custom software is written.

How does 2-byte slave addressing work?

Since a single byte is normally used to define the slave address and each slave on a network requires a unique address, the number of slaves on a network is limited to 256. The limit defined in the modbus specification is even lower at 247.

To get beyond this limit, a modification can be made to the protocol to use two bytes for the address. The master and the slaves would all be required to support this modification. Two byte addressing extends the limit on the number of slaves in a network to 65535.

By default, the Simply Modbus software uses 1 byte addressing. When an address greater than 255 is entered, the software automatically switches to 2 byte addressing and stays in this mode for all addresses until the 2 byte addressing is manually turned off.

How can you send events and historical data?

Enron Modbus includes commands for moving events and historical data..

What is Enron Modbus?

Enron Modbus is a modification to the standard Modicon modbus communication protocol developed by Enron Corporation.

See Enron Modbus for details.

What else?

If you read this page, We would love to hear your comments.  Please send an email to info@simplymodbus.ca and let us know what you found helpful and what topics we could add, expand or clarify.

Home • FAQ • EnronDownloadPurchaseContact

Copyright © 2024 Simply Modbus. All rights reserved